This is a solution of A/C for a UPS room. The characteristic of the UPS room is the workplace in back-up power facility, and there is a large amount of equipment. Personnel are not too much. According to the characteristics of the space for the UPS room, the selection of model is recommended as HIMOD E16.
經(jīng)濟效益評估:(Economic Evaluation)
一楷象、 該UPS機房需安裝空調(diào)面積總計100平方米左右墓枝,有大量發(fā)熱設(shè)備(15KW),對溫濕控制及節(jié)能有要求诫列,依據(jù)實際情況每平米所需制冷量平均按400W計算垄怯,總需求55KW制冷量水水。
The total area is of about 100 square meters for the UPS room, and there is a large amount of heat source (15KW), and it requires the temperature and humidity control and energy saving features. Required cooling capacity per square meter on average calculated based on the actual situation according to 400W, the total demand for cooling capacity is of 55KW.
二、 要滿足該項目50KW的制冷量迂卢,需使用HIMOD E16機組1套裝機某弦。
To meet the cooling capacity of 55KW, this project is needed to use one set of unit (HIMOD E16).
三、 經(jīng)濟效益對比估算:傳統(tǒng)空調(diào)滿足55KW制冷量的輸入功率至少為21KW左右而克,而HIMOD E16機組1套主機的輸入功率合計為14.07KW靶壮,主機部分省電33%,全年共計節(jié)省電費1.3萬元以上员萍。(按1年運行8個月腾降,1月運行30天,1天運行8小時碎绎,用電按1元1度計算)
Comparison of economic benefit estimation: the traditional air-conditioning input power (55KW cooling capacity) is at least about 21KW, and the HIMOD E16 input power per set is of 14.07KW. The energy saving is up to 33%. The annual saving is more than 13000 CNY. (According to 8 months per year, 30 days per month, 8 hours per day of operation, electricity by 1 CNY/1 degree calculation)