針對小型數(shù)據(jù)中心的空調(diào)解決方案媚送,數(shù)據(jù)中心的特點為資料處理工作場所留绞,數(shù)據(jù)中心有大量發(fā)熱設(shè)備,數(shù)據(jù)中心內(nèi)人員不會太多。根據(jù)小型數(shù)據(jù)中心的特點坡沿,空調(diào)選型推薦如下:HIMOD P16機型炫茄。
This is a solution of A/C for a small data center. The characteristic of the small data center is the workplace in data processing facility, and there is a large amount of equipment. Personnel are not too much. According to the characteristics of the space for the small data center, the selection of model is recommended as HIMOD P16.
經(jīng)濟效益評估:(Economic Evaluation)
一、 該小型數(shù)據(jù)中心需安裝空調(diào)面積總計100平方米左右苍息,有大量發(fā)熱設(shè)備(12KW)源譬,對溫濕控制及節(jié)能有要求集惋,依據(jù)實際情況每平米所需制冷量平均按350W計算孕似,總需求47KW制冷量踩娘。
The total area is of about 100 square meters for the small data center, and there is a large amount of heat source (12KW), and it requires the temperature and humidity control and energy saving features. Required cooling capacity per square meter on average calculated based on the actual situation according to 350W, the total demand for cooling capacity is of 47KW.
二、 要滿足該項目47KW的制冷量喉祭,需使用HIMOD P16機組1套裝機养渴。
To meet the cooling capacity of 47KW, this project is needed to use one set of unit (HIMOD P16).
三、 經(jīng)濟效益對比:傳統(tǒng)空調(diào)滿足47KW制冷量的輸入功率至少為16KW左右抛惶,而HIMOD P16機組1套主機的輸入功率合計為10.5KW伍茎,主機部分省電34.5%斥稍,全年共計節(jié)省電費1萬元以上。(按1年運行8個月已清,1月運行30天态晤,1天運行8小時,用電按1元1度計算)
Comparison of economic benefits: the traditional air-conditioning input power (47KW cooling capacity) is at least about 16KW, and the HIMOD P16 input power per set is of 10.5KW. The energy saving is up to 34.5%. The annual saving is more than 10000 CNY. (According to 8 months per year, 30 days per month, 8 hours per day of operation, electricity by 1 CNY/1 degree calculation)